List Price: CAD 141.13 CAD 77.62 -45%
• Key removable in either position
• Disablement of panel and solenoid circuit when activation
• UL listed, CFSM Approved
Datasheet Add to cart• Meets requirements of NFPA 72 and 2001
• Colored LEDs indicate system status
• Stainless steel plate mounts to single gang
box
• RCDS-1: key removable in both positions
• RCDS-2001: key only removable in enabled
position to comply with NFPA 2001
• Compatible with any 24VDC system
The device consists of a stainless steel faceplate, green LED,
amber LED, and a switch assembly. It is designed to mount
on a standard single gang electrical enclosure.
Application
The RCDS-1 complies with the requirements of NFPA 72
(National Fire Alarm and Signaling Code):
The RCDS-2001 complies with the requirements of NFPA
2001 (Standard on Clean Agent Fire Extinguishing Systems):
• Specifying a physical switch to disconnect the release
circuit in place of a software controlled disconnect.
• Creating a supervisory condition on the associated
release panel.