Columbia Panel (conventional system)

C2WT-BA SMOKE/HEAT COMBO DETECTOR (ULC LISTED) ODUC2WT-C

List Price: CAD 105.60 CAD 58.08 -45%

Photoelectric and photoelectric/ thermal smoke detectors represent a significant advancement in conventional detection, incorporating three key features: installation ease, intelligence, and instant inspection. 

Add to cart

MAIN FEATURES

 

• Plug-in detector line — mounting base included.
• Large wire-entry port.
• In-line terminals with SEMS screws.
• Mounts to octagonal and single-gang backboxes, 4" (101.6
mm) square backboxes, or directly to ceiling.
• Stop-Drop ’N Lock attachment to base.
• Removable detector cover and chamber for easy cleaning.
• Built-in remote maintenance signaling.
• Drift compensation and smoothing algorithms.
• Simplified sensitivity measurement.
• Wide-angle, dual-color LED indication.
• Loop testing via “EZ Walk” feature.
• Built-in test switch.

DESCRIPTION

Installation ease. The i³ Series redefines installation ease with its plug-in design. This allows an installer to pre-wire the bases included with the heads. The large wire-entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of backbox mounting methods, as well as direct mounting with drywall anchors. To complete the installation, i³ Series heads plug into the base with a simple Stop-Drop ’N Lock™ action.

Intelligence. i³ Series detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms, to minimize nuisance alarms, are standard in the i³ Series. When connected to the 2W-MOD loop test/maintenance module, two-wire i³ detectors are capable of generating a remote maintenance signal when they need cleaning. This signal is indicated by LEDs located at the module and at the panel. To read the sensitivity of i³ detectors, the SENS-RDR is a wireless device that displays sensitivity in terms of percent-per-foot obscuration.

Instant inspection. The i³ Series provides wide-angle red and green LED indicators for instant inspection of detector condition. The LEDs indicate: normal standby, out-of-sensitivity, alarm, or freeze trouble conditions. The “EZ Walk” loop test feature is available on two-wire i³ Series detectors when connected to the 2W-MOD loop test/maintenance module. The
“EZ Walk” feature verifies the initiating loop wiring by providing
LED status indication at each detector.

SPECIFICATION

PHYSICAL SPECIFICATIONS

Operating Temperature Range: For models 2W-B and 4W-B:
32°F to 120°F (0°C to 49°C); for thermal models 2WT-B and
4WT-B: 32°F to 100°F (0°C to 37.8°C).
Operating Humidity Range: 0% – 95% RH, non-condensing.
Thermal Sensor: 135°F (57.2°C) fixed (models 2WT-B,
4WT-B).

Freeze Trouble: 41°F (5°C) (models 2WT-B and 4WT-B).
Sensitivity: 2.5%/foot (0.762%/meter) nominal.
Input Terminals: Utilize 14 to 22 AWG wire.
Dimensions (including base): 5.3" (134.62 mm) diameter,
2.0" inches (50.8 mm) high.
Weight: 6.3 oz. (178.6 grams).
Mounting Options: 3.5" (88.9 mm) octagonal backbox; 4"
(101.6 mm) octagonal backbox; single-gang backbox; 4"
(101.6 mm) square backbox with a plaster ring; or direct mount
to ceiling.


ELECTRICAL SPECIFICATIONS


Operating Voltage: 12/24 V non-polarized nominal; 8.5 V
minimum; 35 V maximum.
Maximum Alarm Current” For two-wire models: 130 mA limited
by control panel; For four-wire models: 20 mA @ 12 V, 23
mA @ 24 V.
Alarm Contact Ratings: For four-wire models: 0.5 A @ 30
VAC/VDC; not applicable for two-wire models.

 